| Capacity |
Cold |
kW |
16.00 |
| Warm |
kW |
18.00 |
| Power supply |
~ 380-415V/50Hz/3Ph |
| Rated input |
Cold |
kW |
5.60 |
| Warm |
kW |
5.20 |
| Current rate |
Cold |
A |
11.60 |
| Warm |
A |
11.40 |
| Energy efficiency |
EER (Cold) |
kW/kW |
2.85 |
| C.O.P. (Warm) |
kW/kW |
3.46 |
| Air capacity |
m³/h |
2500/2300/1900/1800 |
| Pressure range |
Indoor unit |
Pа |
0-100 |
| Sound-pressure level |
Indoor unit/Outdoor unit |
dB(А) |
56/52/49/49/61 |
| Refrigerant coolant type |
R410a |
| Dimensions (width/height/depth) |
Indoor unit/Outdoor unit |
mm |
1235х330х830/ 980х1350х410 |
| Weight |
Indoor unit/Outdoor unit |
kg |
56/118 |
| Refrigerant coolant volume |
kg |
4.10 |
| Operational temperature range |
Cold |
°C |
-15 ... +43 |
| Warm |
°C |
-10 ... +24 |
| Fluid pipeline diameter |
mm/inch |
12.70 / 1/2" |
| Gas pipeline diameter |
mm/inch |
19.05 / 3/4" |
| Maximum pipeline level difference |
m |
30 |
| Maximum pipeline length |
m |
30 |
| Distance between the fastening bolts of the outdoor unit |
mm |
572 |
| Number of the interblock strands (for control) |
2*1.0 – up to 20 m long |
| Main power supply area |
Outdoor |
| Number of strands (power supply) |
Indoor unit |
|
3(Ø1.5 mm)/ |
| Outdoor unit |
|
3(Ø4.0 mm) |
| Factory freon fill (for the number of running meters) |
r.m. |
9.5 |
| Quantity of freon per one running meter (surplus. for one running meter) |
gramm/r.m. |
120 |